APCCONTROL(8)		  BSD System Manager's Manual		 APCCONTROL(8)

NAME
     apccontrolapcupsd(8) event handler script

SYNOPSIS
     apccontrol { <event> <ups-name> <connected> <powered> }

DESCRIPTION
     When apcupsd(8) detects anomalies from the UPS being monitored, it trig‐
     gers an event which usually results in one or more calls to the
     apccontrol shell script.  Each event causes apccontrol to take a particu‐
     lar action. These actions default to sane behaviour for all the events
     that apcupsd is likely to encounter. However, you can change the behav‐
     iour of every single action.

     When apcupsd detects an event, it calls the apccontrol script with the
     following four arguments:

     event	 This is the event that occurred. Refer to the list of possi‐
		 ble events below.

     ups-name	 This is the name of the UPS as specified in the
		 /etc/apcupsd/apcupsd.conf configuration file - not the name
		 in the EEPROM of a smart UPS.

     connected	 This is 1 if apcupsd is connected to the UPS via a serial or
		 USB port.  In the case of a slave machine where apcupsd is
		 not directly connected to the UPS, this value will be 0.

     powered	 This is 1 if the computer on which apcupsd is running is pow‐
		 ered by the UPS and 0 if not. This is not currently imple‐
		 mented and always defaults to 0.

     Events are sent to the system log and, optionally, to the temporary
     events file (/etc/apcupsd/apcupsd.events), and they also generate a call
     to apccontrol which in turn will call any scripts you have placed in the
     /etc/apcupsd directory.

   LIST OF EVENTS AND DEFAULT ACTIONS
     annoyme	  apcupsd generates this event when a shutdown is scheduled,
		  and the time specified by the ANNOYME configuration direc‐
		  tive in the /etc/apcupsd/apcupsd.conf file has expired.

		  Default action -- sends "Power problems please logoff." to
		  wall(1) and then exits.

     battattach	  apcupsd generates this event when it detects that the UPS
		  battery has been reconnected after a battdetach event.

		  Default action: does nothing.

     battdetach	  apcupsd generates this event when it detects that the UPS
		  battery has been disconnected.

		  Default action: does nothing.

     changeme	  apcupsd generates this event when it detects that the util‐
		  ity power is on, but the battery is not functioning cor‐
		  rectly. This is repeated every 9 hours.

		  Default action -- sends "Emergency! UPS batteries have
		  failed Change them NOW" to wall and then exits.

     commfailure  apcupsd generates this event each time it loses communica‐
		  tion with the monitored UPS. This event is not detected on
		  simple signalling UPSes like the Back-UPS 650.

		  Default action -- sends "Communications with UPS lost." to
		  wall and then exits.

     commok	  apcupsd generates this event after a commfailure event when
		  communication with the UPS is re-established.

		  Default action -- sends "Communications with UPS restored."
		  to wall and then exits.

     doreboot	  This event is deprecated and should not be used.

		  Default action -- sends "Beginning Reboot Sequence" to wall
		  and then calls shutdown(8) with the "-r now" command line
		  arguments to reboot the computer.

     doshutdown	  apcupsd generates this event to shutdown the computer when
		  the UPS is running on battery power and one of the limits
		  (time, run, load) is reached.

		  Default action -- sends "Beginning Shutdown Sequence" to
		  wall and then calls shutdown(8) with the command line argu‐
		  ments "-h now" to shutdown the computer.

     emergency	  apcupsd generates this event when the UPS is on battery
		  power, the battery is low and the utility power is on: a
		  sure sign of battery failure!

		  Default action -- sends "Emergency Shutdown. Possible UPS
		  battery failure."  to wall. Immediately after this, apcupsd
		  generates a doshutdown event to shutdown the system.

     failing	  apcupsd generates this event when the UPS is running on bat‐
		  teries and the UPS sets the low battery signal indicating
		  that battery power is nearly exhausted. After this event,
		  apcupsd will immediately generate a doshutdown event.

		  Default action -- sends "UPS battery power exhausted. Doing
		  shutdown." to wall and then exits.

     killpower	  apcupsd does not normally generate this event. Instead, it
		  is invoked directly from the system halt script as 'apccon‐
		  trol killpower' because the killpower event needs to be per‐
		  formed as late in system shutdown as possible.

		  Default action -- sends "UPS now committed to shut down" to
		  wall, waits for 10 seconds and then issues the command
		  "apcupsd --killpower" to put the UPS into hibernate mode and
		  shut off power to the connected equipment.  In the case of a
		  smart UPS, the UPS will then wait for the expiry of any con‐
		  figured shutdown time delay specified by the SLEEP configu‐
		  ration directive.  In hibernate mode, the UPS will restore
		  utility power to the connected equipment subject to the val‐
		  ues specified for the RETURNCHARGE and WAKEUP configuration
		  directives.

     loadlimit	  apcupsd generates this event when the battery discharge
		  limit specified by the BATTERYLEVEL configuration directive
		  has been reached.

		  Default action -- sends "UPS battery discharge limit
		  reached. Doing shutdown" to wall and then exits. After this
		  event, apcupsd will immediately generate a doshutdown event.

     mainsback	  apcupsd generates this event when the utility power returns
		  after a powerout event. The doshutdown event may or may not
		  have been generated depending on the parameters you have
		  defined and the length of the power outage. Attempting can‐
		  cellation of a doshutdown event should never be tried as it
		  is very unlikely to succeed and will almost certainly leave
		  your computer in an indeterminate state.

		  Default action -- if the file /var/run/powerfail exists,
		  sends "Continuing with shutdown." to wall and then exits.
		  Otherwise, does nothing.

     onbattery	  apcupsd generates this event if a power failure has been
		  detected and the UPS is still on battery power at the expiry
		  of the delay specified by the ONBATTERYDELAY configuration
		  directive.

		  Default action -- sends "Power failure. Running on UPS bat‐
		  teries." to wall and then exits.

     offbattery	  apcupsd generates this event when the utility power returns
		  if, and only if, the onbattery event has been generated.

		  Default -- sends ""Power has returned..." to wall and then
		  exits.

     powerout	  apcupsd generates this event as soon as apcupsd detects that
		  the UPS has switched to battery power and it is not a self-
		  test.

		  Default action -- does nothing.

     remotedown	  apcupsd generates this event on a slave machine when it
		  detects either (1) that the master has shutdown, or (2) that
		  an onbattery event has occurred and communication with the
		  master has been lost.

		  Default action: sends "Remote Shutdown. Beginning Shutdown
		  Sequence." to wall and exits. Immediately after this,
		  apcupsd generates a doshutdown event to shutdown the system.

     runlimit	  apcupsd generates this event when the remaining runtime
		  limit specified by the MINUTES configuration directive
		  expires while the UPS is on battery power as the result of a
		  utility power outage. The remaining runtime is internally
		  calculated by the UPS and monitored by apcuspd.

		  Default action -- sends "UPS battery runtime percent
		  reached. Doing shutdown."  to wall and then exits. After
		  this event, apcupsd will immediately generate a doshutdown
		  event.

     timeout	  apcupsd generates this event when the time specified by the
		  TIMEOUT configuration directive expires while the UPS is on
		  battery power as the result of a utility power outage. This
		  configuration directive is not normally used with smart
		  UPSes which would instead rely on the more reliable remain‐
		  ing runtime (MINUTES) or the battery level (BATTERYLEVEL)
		  configuration directives.

		  Default action -- send "UPS battery runtime limit exceeded.
		  Doing shutdown."  to wall and then exits. After this event,
		  apcupsd will immediately generate a doshutdown event.

     startselftest apcupsd generates this event when it detects the start of a
		  UPS self test.

		  Default action: does nothing.

     endselftest  apcupsd generates this event when it detects the end of a
		  UPS self test.

		  Default action: does nothing.

   CUSTOMISING EVENT ACTIONS
     Do not modify apccontrol directly as it will be overwritten the next time
     you upgrade to a new release of apcupsd.

     The recommended way to customise an event action is simply to create an
     executable program or script file with the same name as the event and put
     that file in the /etc/apcupsd directory. Now, when the selected event
     occurs, apccontrol will execute your program or script.

     If you want apccontrol to also execute its default action for the
     selected event, your program or script should exit with an exit status of
     0 (zero).

     If you do not want apccontrol to also execute its default action for the
     selected event, your program or script must exit with an exit status of
     99. Be aware that if you completely override the default action, you must
     ensure the proper shutdown of your computer if this is necessary.

     Some sample scripts (changeme, commfailure, commok, offbattery and onbat‐
     tery) that email messages to root instead of broadcasting messages to all
     logged-in users may be found in /etc/apcupsd after an installation and
     also in the platforms/etc directory of the apcupsd source code.

FILES
     /etc/apcupsd/apccontrol

SEE ALSO
     wall(1), apcupsd.conf(5), apcupsd(8), shutdown(8).

     The HTML apcupsd manual installed on your system or available online at
     http://www.apcupsd.org/

AUTHORS
   This page
     Trevor Roydhouse

   Software
     Adam Kropelin (current Project Manager and Code Maintainer)
     Kern Sibbald (former Project Manager and Code Maintainer)
     Riccardo Facchetti (former Project Manager and Code Maintainer)
     Andre M. Hedrick (Project Founder and former Code Maintainer)

   Contributors
     An enormous number of users who have devoted their time and energy to
     this project -- thanks.

apccontrol v3.14.6	       January 10, 2009		    apccontrol v3.14.6
[top]

List of man pages available for DragonFly

Copyright (c) for man pages and the logo by the respective OS vendor.

For those who want to learn more, the polarhome community provides shell access and support.

[legal] [privacy] [GNU] [policy] [cookies] [netiquette] [sponsors] [FAQ]
Tweet
Polarhome, production since 1999.
Member of Polarhome portal.
Based on Fawad Halim's script.
....................................................................
Vote for polarhome
Free Shell Accounts :: the biggest list on the net