blazer man page on SuSE

Man page or keyword search:  
man Server   14857 pages
apropos Keyword Search (all sections)
Output format
SuSE logo
[printable version]

BLAZER(8)			  NUT Manual			     BLAZER(8)

NAME
       blazer - Driver for Megatec/Q1 protocol serial (blazer_ser) and USB
       (blazer_usb) based UPS equipment

NOTE
       This man page only documents the hardware-specific features of the
       blazer driver. For information about the core driver, see nutupsdrv(8).

SUPPORTED HARDWARE
       The blazer driver is known to work with various UPSes from Blazer,
       Energy Sistem, Fenton Technologies, Mustek and many others. The NUT
       compatibility table lists all the known supported models. Keep in mind,
       however, that other models not listed there may also be supported, but
       haven’t been tested.

       All devices with a serial interface (use the blazer_ser driver) and
       many with a USB interface (use the blazer_usb driver) are supported.

EXTRA ARGUMENTS
       You may need to override or provide defaults for some values, depending
       on the make and model of your UPS. The following are the ones that most
       likely will need changing (see ups.conf(5)):

       default.battery.voltage.high = value
	   Maximum battery voltage that is reached after about 12 to 24 hours
	   charging. If you want the driver to report a guesstimated
	   battery.charge, you need to specify this (see BATTERY CHARGE).

       default.battery.voltage.low = value
	   Minimum battery voltage just before the UPS automatically shuts
	   down. If you want the driver to report a guesstimated
	   battery.charge, you need to specify this (see BATTERY CHARGE).

       default.battery.voltage.nominal = value,
       override.battery.voltage.nominal = value
	   Some devices show a wrong nominal battery voltage (or none at all),
	   so you may need to override or set a default value.

       override.battery.packs = value
	   Some devices report a part of the total battery voltage. For
	   instance, if battery.voltage.nominal is 24 V, but it reports a
	   battery.voltage of around 2 V, the number of battery.packs to
	   correct this reading would be 12. The driver will attempt to detect
	   this automatically, but if this fails somehow, you may want to
	   override this value.

       ondelay = value
	   Time to wait before switching on the UPS (minutes). Note that a
	   value below 3 minutes, may cause earlier firmware versions to not
	   switch on automatically, so it defaults to 3 minutes.

       offdelay = value
	   Time to wait before shutting down the UPS (seconds). This value is
	   truncated to units of 6 seconds (less than 60 seconds) or 60
	   seconds (more than 60 seconds). Defaults to 30 seconds.

       norating
	   Some UPSes will lock up if you attempt to read rating information
	   from them. Setting this flag will make the driver skip this step.

       novendor
	   Some UPSes will lock up if you attempt to read vendor information
	   from them. Setting this flag will make the driver skip this step.

       protocol = string
	   Skip autodetection of the protocol to use and only use the one
	   specified. Supported values megatec, megatec/old, mustek and zinto.

       runtimecal = value,value,value,value
	   Parameter used in the (optional) runtime estimation. This takes two
	   runtimes at different loads. Typically, this uses the runtime at
	   full load and the runtime at half load. For instance, if your UPS
	   has a rated runtime of 240 seconds at full load and 720 seconds at
	   half load, you would enter

	       runtimecal = 270,100,720,50

	   The first load should always be higher than the second. If you have
	   values available for loads other than 100 and 50 % respectively,
	   you can use those too, but keep them spaced apart as far as
	   reasonably possible. Just don’t get too close to no load
	   (prediction of runtime depends more on idle load for the battery
	   then).

       chargetime = value
	   The time needed to fully recharge the battery after being fully
	   discharged. If not specified, the driver defaults to 43200 seconds
	   (12 hours). Only used if runtimecal is also specified.

       idleload = value
	   Minimum battery load used by the driver to estimate the runtime. If
	   not specified, the driver defaults to 10%. Only used if runtimecal
	   is also specified.

SERIAL INTERFACE ONLY
       cablepower = string
	   By default the driver will set DTR and clear RTS (normal). If you
	   find that your UPS isn’t detected or the communication with the UPS
	   is unreliable, you may try if clear DTR and set RTS (reverse), set
	   DTR and RTS (both) or clear DTR and RTS (none) improves this
	   situation.

USB INTERFACE ONLY
       vendorid = regex, productid = regex, vendor = regex, product = regex,
       serial = regex
	   Select a specific UPS, in case there is more than one connected via
	   USB. Each option specifies an extended regular expression (see
	   regex(7)) that must match the UPS’s entire vendor/product/serial
	   string (minus any surrounding whitespace), or the whole 4-digit
	   hexadecimal code for vendorid and productid. Try -DD for finding
	   out the strings to match.

       Examples:

	   -x vendor="Foo.Corporation.*"

	   -x vendorid=051d    # (APC)

	   -x product=".*(Smart|Back)-?UPS.*"

       bus = regex
	   Select a UPS on a specific USB bus or group of busses. The argument
	   is a regular expression that must match the bus name where the UPS
	   is connected (e.g. bus="002", bus="00[2-3]").

       subdriver = string
	   Select a serial-over-USB subdriver to use. You have a choice
	   between phoenix, ippon, cypress, and krauler. When using this
	   option, it is mandatory to also specify the vendorid and productid.

UPS COMMANDS
       This driver supports some instant commands (see upscmd(8)):

       beeper.toggle
	   Toggle the UPS beeper. (Not available on some hardware.)

       load.on
	   Turn on the load immediately.

       load.off
	   Turn off the load immediately (see KNOWN PROBLEMS).

       shutdown.return [value]
	   Turn off the load and return when power is back. Uses the timers
	   defined by ondelay and offdelay.

       shutdown.stayoff [value]
	   Turn off the load and remain off (see KNOWN PROBLEMS). Uses the
	   timer defined by offdelay.

       shutdown.stop
	   Stop a shutdown in progress.

       test.battery.start.deep
	   Perform a long battery test (Not available on some hardware.)

       test.battery.start.quick
	   Perform a (10 second) battery test.

       test.battery.start value
	   Perform a battery test for the duration of value seconds (truncated
	   to units of 60 seconds).

       test.battery.stop
	   Stop a running battery test (not available on some hardware.)

BATTERY CHARGE
       Due to popular demand, this driver will report a guesstimated
       battery.charge and optionally battery.runtime, provided you specified a
       couple of the EXTRA ARGUMENTS listed above.

       If you specify both battery.voltage.high and battery.voltage.low in
       ups.conf(5), but don’t enter runtimecal, it will guesstimate the state
       of charge by looking at the battery voltage alone. This is not reliable
       under load, as this only gives reasonably accurate readings if you
       disconnect the load, let the battery rest for a couple of minutes and
       then measure the open cell voltage. This just isn’t practical if the
       power went out and the UPS is providing power for your systems.

				battery.voltage - battery.voltage.low
	   battery.charge =  ------------------------------------------ x 100 %
			     battery.voltage.high - battery.voltage.low

       There is a way to get better readings without disconnecting the load
       but this requires to keep track on how much (and how fast) current is
       going in- and out of the battery. If you specified the runtimecal, the
       driver will attempt to do this. Note however, that this heavily relies
       on the values you enter and that the UPS must be able to report the
       load as well. There are quite a couple of devices that report 0 % (or
       any other fixed value) at all times, in which case this obviously
       doesn’t work.

       The driver also has no way of determining the degradation of the
       battery capacity over time, so you’ll have to deal with this yourself
       (by adjusting the values in runtimecal). Also note that the driver
       guesses the initial state of charge based on the battery voltage, so
       this may be less than 100 %, even when you are certain that they are
       full. There is just no way to reliably measure this between 0 and 100 %
       full charge.

       This is better than nothing (but not by much). If any of the above
       calculations is giving you incorrect readings, you are the one that put
       in the values in ups.conf(5), so don’t complain with the author. If you
       need something better, buy a UPS that reports battery.charge and
       battery.runtime all by itself without the help of a NUT driver.

NOTES FOR THE PREVIOUS USER OF MEGATEC DRIVERS
       The blazer drivers having replaced the megatec ones, some configuration
       changes may be required by users switching to blazer.

       Part of this, the following megatec options, in ups.conf, have to be
       changed:

       battvolts
	   You need to use default.battery.voltage.high and
	   default.battery.voltage.low

       dtr and rts
	   You need to use cablepower

       ignoreoff
	   This parameter can simply be discarded, since it was a wrong
	   understanding of the specification.

KNOWN PROBLEMS
       Some UPS commands aren’t supported by all models. In most cases, the
       driver will send a message to the system log when the user tries to
       execute an unsupported command. Unfortunately, some models don’t even
       provide a way for the driver to check for this, so the unsupported
       commands will silently fail.

       Both the load.off and shutdown.stayoff instant commands are meant to
       turn the load off indefinitely. However, some UPS models don’t allow
       this.

       Some models report a bogus value for the beeper status (will always be
       enabled or disabled). So, the beeper.toggle command may appear to have
       no effect in the status reported by the driver when, in fact, it is
       working fine.

       The temperature and load value is known to be bogus in some models.

AUTHORS
       Arjen de Korte <adkorte-guest at alioth.debian.org>, Alexander Gordeev
       <lasaine at lvk.cs.msu.su>

SEE ALSO
       nutupsdrv(8), upsc(8), upscmd(8), upsrw(8)

   Internet Resources:
       The NUT (Network UPS Tools) home page: http://www.networkupstools.org/

Network UPS Tools		  09/15/2011			     BLAZER(8)
[top]

List of man pages available for SuSE

Copyright (c) for man pages and the logo by the respective OS vendor.

For those who want to learn more, the polarhome community provides shell access and support.

[legal] [privacy] [GNU] [policy] [cookies] [netiquette] [sponsors] [FAQ]
Tweet
Polarhome, production since 1999.
Member of Polarhome portal.
Based on Fawad Halim's script.
....................................................................
Vote for polarhome
Free Shell Accounts :: the biggest list on the net