NETXML-UPS(8)			  NUT Manual			 NETXML-UPS(8)

NAME
       netxml-ups - Driver for Eaton / MGE Network Management Card / Proxy
       (XML/HTTP Protocol) equipment

NOTE
       This man page only documents the hardware-specific features of the
       netxml-ups driver. For information about the core driver, see
       nutupsdrv(8).

SUPPORTED HARDWARE
       netxml-ups support all recent Eaton / MGE models which use a Network
       Management Card or Proxy (MGE XML/HTTP protocol based). This applies to
       both Eaton (previously MGE Office Protection Systems) and to MGE UPS
       SYSTEMS. Supported card and proxy models are:

       ·   NMC Minislot (Ref 66102, firmware EA or newer),

       ·   SNMP/Web Minislot card (Ref 66244)

       ·   NMC Transverse (Ref 66074),

       ·   NMC & Modbus/JBus (Ref 66103),

       ·   Network Management Proxy,

       ·   ePDU Monitored (newer version).

       Older models, such as SNMP card (Ref 66062 and Ref 66045), use the SNMP
       protocol and should use the snmp-ups(8) driver with the "mibs=mge"
       parameter.

EXTRA ARGUMENTS
       This driver supports the following optional settings in the
       ups.conf(5):

       timeout=value
	   The timeout for connecting to and reading from the UPS. Defaults to
	   5 seconds. Don’t change this value unless you know exactly what
	   you’re doing.

       This value must never be higher than half the MAXAGE value specified in
       upsd.conf(5), otherwise you run the risk that upsd(8) declares the
       driver stale while it is waiting for a connection to timeout.

       login=value
	   Set the login value for authenticated mode. This feature also needs
	   the password argument, and allows value settings in the card. This
	   feature is not used yet.

       password=value
	   Set the password value, needed with the login for authenticated
	   mode. This feature is not used yet.

IMPLEMENTATION
       The hostname of the UPS is specified with the "port" value in ups.conf,
       i.e.:

	   [mgexml]
		   driver = netxml-ups
		   port = http://netxml-ups.example.com:80

       Specifying the method to connect to the UPS (http, https) is mandatory.
       If the port is equal to the default for the method specified (80 for
       http, 443 for https) it may be omitted.

       In order not to overload older NMCs by polling them too frequently, it
       is recommended to increase the "pollinterval" (see nutupsdrv(8)) and
       ups.conf(5)) to at least 5 seconds.

KNOWN ISSUES
       Don’t connect to the UPS through a proxy. Although it would be trivial
       to add support for proxies, this is not recommended and don’t ask for
       it. Not only because it will prevent the driver to make a persistent
       connection to the UPS, but also it adds an additional failure mode. If
       the proxy goes down (for whatever reason), the driver will no longer be
       able to reach the UPS.

AUTHORS
       Arjen de Korte <adkorte-guest@alioth.debian.org>

SEE ALSO
   The core driver:
       nutupsdrv(8)

   Internet resources:
       The NUT (Network UPS Tools) home page: http://www.networkupstools.org/

Network UPS Tools		  09/15/2011			 NETXML-UPS(8)
[top]

List of man pages available for SuSE

Copyright (c) for man pages and the logo by the respective OS vendor.

For those who want to learn more, the polarhome community provides shell access and support.

[legal] [privacy] [GNU] [policy] [cookies] [netiquette] [sponsors] [FAQ]
Tweet
Polarhome, production since 1999.
Member of Polarhome portal.
Based on Fawad Halim's script.
....................................................................
Vote for polarhome
Free Shell Accounts :: the biggest list on the net